ESP32 Modbus Module

Overview

The ESP32 Modbus module is designed for integrating Modbus-enabled devices with Home Assistant. It supports various devices including:

  • Nilan Ventilation (CTS602/602Light and CTS400 with Modbus)
  • Wavin AHC9000 (Floor heating)
  • Wavin Sentio (Floor heating)
  • EM340 (Electricity meter with Modbus)
  • NIBE F1255 (Heatpump)

The module is flexible and can be adapted for other Modbus applications, although no promises are made for unsupported devices.

Buy the module here


Disclaimer

Use at your own risk! Improper connections could potentially damage hardware. The hardware and software have been tested with the listed devices without issues.


Features

  • Modbus communication with popular home automation systems (e.g., Home Assistant, ESPHome).
  • Supports multiple devices (Nilan, Wavin, EM340, NIBE, and more).
  • Provides wiring and software guides to get started quickly.

Rev2 hardware

The 2 x optocoupler outputs have been removed (legacy functionality), the 2 x pin rows are gone, and the flow-control pin is GPIO3.

The Rev2 code is here: rev2

Using the older Rev1 board? The Rev1 example code (flow-control pin GPIO10) is still available in esphome_example_code/rev1.

Case

Topview

Schematic

Wavin AHC9000 automatic zones

For the Wavin AHC9000, use the ready-made automatic-zone configuration for the Rev2 module:

ahc9000_v4_auto.yaml

This YAML sets up the wavinahc9000v4 ESPHome component, automatic zone discovery, and the services required by the companion Home Assistant integration. It is already configured for the Rev2 flow-control pin (GPIO3).

  1. Wire the AHC9000 to the module as described in Connecting the Module.
  2. Flash ahc9000_v4_auto.yaml with ESPHome.
  3. Install the Wavin Floor Heating integration. Home Assistant normally discovers the module automatically, so no IP address is required.

Component documentation and all YAML options: Wavin AHC9000 V4 setup

Wavin Sentio automatic rooms

For the Wavin Sentio, use the automatic room-discovery configuration:

Configuration: WavinSentioV2_example.yaml

It uses the sentiov2 component and publishes a topology text sensor for the same Home Assistant integration. Install the Wavin Floor Heating integration after flashing.

Component documentation and YAML options: Wavin Sentio V2 setup

Nilan ventilation automatic detection

For Nilan CTS602, CTS602 Light and CTS400 ventilation units, use the automatic detection and commissioning configuration.

Wiring: the module's RJ45 socket is not wired like a Nilan RJ45 port. For the exact cable and pinout for the Rev2 module, see the dedicated Nilan connection guide.

Configuration: nilan_ventilation_auto.yaml

The firmware detects the controller, model and capabilities, prunes registers the unit does not support and publishes topology/values/status for the companion Home Assistant integration. The Nilan bus runs at 19200 baud, 8 data bits, even parity, 1 stop bit and Modbus address 30.

Install the Nilan Ventilation integration after flashing. Home Assistant normally discovers the module automatically, so no IP address is required.

Component documentation and YAML options (currently on the testing branch): auto_nilan setup

The older manual examples (nilan602.yaml, Nilan_cts400.yaml, Nilan_example.yaml) remain for legacy setups.

Connecting the Module

General connector layout

The module's RJ45 socket uses the Wavin pinout:

Pin Function
1, 2 GND
3 B (Modbus−)
4, 5 not used
6 A (Modbus+)
7, 8 +12 V input (5–24 V DC)

Power the module with USB-C, or with 5–24 V DC on pins 7/8. Do not use both at the same time.

Connections

Compatibility notes

Device Connection
Wavin AHC9000 / Sentio Straight RJ45 patch cable. The Wavin display must be disconnected because it is also a Modbus master.
Nilan CTS400 / CTS602 / CTS602 Light The module's RJ45 is not the Nilan pinout. Use the Nilan connection guide.
EM340 Connect A/B/GND as shown below.
Nibe F1255 Connect A/B/GND as shown below.

Wavin AHC9000 / Sentio

Use a straight RJ45 patch cable between the Wavin Modbus port and the module.

Only one Modbus master is allowed on the bus. Disconnect the Wavin display/controller before connecting the module, because the display also acts as a Modbus master. The module must be the only master.

For the ready-made configurations, see Wavin AHC9000 automatic zones and Wavin Sentio automatic rooms.

Nilan

The module's RJ45 socket is not wired like a Nilan RJ45 port. A straight patch cable will not work. Use the dedicated Nilan connection guide for the exact cable and pinout for CTS400, CTS602 and CTS602 Light.

EM340

A wiring example on an EM340 Modbus power meter:

Connections

Nibe F1255

A Nibe heat pump Modbus interface:

Connections


Software Guides

Installation & Setup

Example Code

You can find example code for Nilan, Nibe, EM340, and more in the code folder. A generic setup for Nilan is available here.

Example configuration for Nilan:

esphome:
  name: nilan
esp32:
  board: esp32-c3-devkitm-1
  framework:
    type: arduino

wifi:
  ssid: !secret wifi_ssid
  password: !secret wifi_password
  output_power: "8.5"

uart:
  rx_pin: 20
  tx_pin: 21
  parity: EVEN
  baud_rate: 19200
  id: uart_modbus
  stop_bits: 1
  
modbus:
  id: modbus_id
  flow_control_pin: 10
  uart_id: uart_modbus