vix-driver

Python driver for Parker ViX250IM / ViX500IM microstepper indexer drives over RS232. It uses the drives' EASI-V ASCII command set.

Written from the ViX250IM & ViX500IM Microstepper RS232 Indexer Drive User Guide (Parker 1600.324.01b, Feb 2004, firmware 2.0 onwards). The guide is not included here; Parker publishes it at https://www.parkermotion.com/manuals/Digiplan/ViX-IM_UG_2-04.pdf.

Install

pip install -e .

The only runtime dependency is pyserial.

Quick start

from vix_driver import ViXBus, Mode

with ViXBus("/dev/ttyUSB0") as bus:            # 9600 8N1 by default
    drive = bus.drive(1)                        # axis address 1..255

    drive.energize()                            # ON, then checks status and faults
    drive.set_motion(velocity=5, acceleration=50)

    drive.move_relative(4000)                   # steps; blocks until done
    drive.move_absolute(0, velocity=10)
    drive.position_target()                     # PT (commanded position)

    drive.jog(2, positive=False)                # continuous mode
    drive.stop()                                # controlled stop (S)
    drive.wait_for_move()

    drive.configure_homing(velocity=-5, acceleration=50, edge_positive=False)
    drive.go_home()

    drive.inputs()                              # (stop, reg, home, lim-, lim+)
    drive.set_output(1, True)

Several drives on one bus

from vix_driver import ViXBus, CommsMode

with ViXBus("/dev/ttyUSB0") as bus:
    bus.discover()                          # {1: '2.1b', 2: '2.1b', 3: '2.1b'}
    bus.set_comms_mode_all(CommsMode.QUIET_ECHO)   # recommended, see below

    x, y = bus.drive(1), bus.drive(2)       # individual drives
    axes = bus.group(1, 2, 3)               # or bus.group() for all discovered

    axes.energize()
    axes.move_relative({1: 4000, 2: -2000, 3: 8000}, velocity=5, acceleration=50)
    axes.move_absolute({2: 0})              # axes not listed stay put
    axes.positions()                        # {1: 4000, 2: 0, 3: 8000}
    axes.drive_faults()                     # {} when all healthy

    bus.stop_all()                          # 0S: controlled stop, every drive
    bus.kill_all()                          # 0K: kill every drive

How replies are matched. Replies carry no address. The bus therefore runs one transaction at a time (safe across threads) and ties each reply to the command that caused it:

  • RS232 daisy chain (default, echo=True). Every command travels round the ring and comes back to the PC. The bus waits for that echo before accepting a reply. Anything that arrives earlier is discarded, such as a late reply to an earlier read or another drive's message. A missing echo is reported as a broken chain. Keep echo on for every drive in the chain (EX = 2 or 3).
  • RS485 multidrop (ViXBus(port, echo=False)). The drives must run with echo off (EX = 0 or 1), so this matching isn't available. After a timeout the bus drains the line briefly before the next command.

Recommended setup: bus.set_comms_mode_all(CommsMode.QUIET_ECHO) (EX=2). Drives then only talk when addressed, so a program running on one drive can't inject text into another drive's reply. Add bus.group().save() to make it permanent.

Groups. DriveGroup commands take one value for all axes or a {address: value} dict.

  • Parameters are set on every axis first, then the G commands go out back to back. The axes start a few milliseconds apart.
  • group.go(simultaneous=True) sends one global 0G. It is only allowed when the group contains every drive found by discover(), because 0G starts every drive on the bus.
  • wait_for_move() watches all axes. If one faults, hits a limit or loses power, the others get a controlled stop and the error is raised, with .address naming the drive. If a G is rejected, axes already started are stopped.

Drives ignore reads on address 0, so the driver refuses them.

API overview (ViXDrive)

Area Methods
Motion move_absolute(), move_relative(), jog(), go(), stop(), kill(), pause(), resume(), wait_for_move()
Parameters set_motion(velocity, acceleration, deceleration, distance), velocity(), acceleration(), deceleration(), distance(), set_mode(), get_mode(), set_direction()
Position position_target(), position_actual(), position_error(), position_incremental(), zero_position()
Status status(), drive_faults(), user_faults(), is_moving(), in_position(), is_busy(), is_energized(), check_faults(), status_report(), revision()
Power energize(), de_energize()
Homing / limits configure_homing(), homing_config(), go_home(), configure_limits(), limits_config()
I/O inputs(), set_outputs(), set_output(), analogue_input()
Profiles define_profile(), use_profile(), current_profile()
Config set_motor(), configure_stall_detect(), configure_scale(), set_command_queuing(), set_comms_mode(), read()/write() for any system variable
Programs run_label(), arm(), list_program(), clear_program()
Persistence save(), reset(), factory_reset()
Raw query(body) and command(body) for anything not wrapped

ViXBus: drive(), drives(), group(), broadcast(), discover(), stop_all(), kill_all(), set_comms_mode_all(). DriveGroup: energize(), de_energize(), set_motion(), move_relative(), move_absolute(), go(), stop(), kill(), wait_for_move(), positions(), status(), drive_faults(), check_faults(), is_moving(), write(), save().

Units are motor steps, rev/s and rev/s² unless SCALE or LOADENC is enabled.

Errors

  • ViXCommandError: the drive replied *E. The driver then reads the UF word, so exc.user_faults says why (e.g. "Drive de-energised"). Reading UF clears it.
  • DriveFaultError: a hardware fault (DF). .terminal is true if the fault needs a power cycle.
  • LimitError: wait_for_move() saw a limit hit (ST bits 13/14).
  • ViXTimeoutError: no reply, or the move didn't finish in time.

Things to know about the drive

  • Command queuing (CQ). With CQ=1, the factory default, commands sent during a move are buffered until the move ends. That includes position reads. Only K, S, C, R(ST), R(DF), R(UF) and R(RB) answer immediately. wait_for_move() therefore polls R(ST). To read position mid-move, call drive.set_command_queuing(False).
  • PT vs PA. Without an encoder on X2, use position_target() (PT). PA and PE need an encoder.
  • Echo. Create the bus with echo=True (the default) when the drives echo (EX = 2 or 3, the RS232 default), and echo=False when they don't (EX = 0 or 1, the RS485 default). See "Several drives on one bus".
  • Enable input. X4 pin 11, with polarity set by ES, must be active or ON fails with DF bit 21.
  • Mode P makes the drive act as a step/direction base drive. ON/OFF are then prohibited.
  • Saving. After MOTOR, BR (baud) or address changes, call save() then reset().

Bliss

vix_driver.bliss_vix.ViX is a Bliss motor controller: one controller per serial line, one axis per drive. See examples/bliss_vix.yml.

- plugin: generic
  class: ViX
  package: vix_driver.bliss_vix
  serial: {url: /dev/ttyS0, baudrate: 9600}
  axes:
    - {name: tth, address: 1, steps_per_rev: 4000, steps_per_unit: 4000,
       velocity: 1, acceleration: 10}

Install this package into the Bliss environment (pip install -e .).

Supported: moves, group moves (move(tth, 30, th, 15)), stop/Ctrl-C, jog, axis.on()/off(), home(), hw_limit(), read-only X2 encoders, and raw_write_read("1R(PT)"). Custom commands: tth.vix_status(), tth.vix_faults() and tth.vix_inputs().

Behaviour to be aware of:

  • Position. The position is the drive's commanded position PT in motor steps. The drive can only reset it to 0, so axis.dial = 0 works and other dial values are refused. User offsets (axis.position = x) work as usual.
  • Units. Velocity and acceleration are converted from Bliss steps/s to the drive's rev/s using steps_per_rev. At start-up that value is checked against the motor resolution reported by the drive, and a mismatch aborts.
  • Command queuing. The controller sets CQ=0 on each drive so position and state can be polled during moves. It does this again after every axis.on(), which also re-sends velocity and acceleration.
  • Power cycles. A power-cycled or faulted drive comes back de-energised (state OFF or FAULT) with its position reset. Run axis.on() and then axis.sync_hard(); Bliss refuses to move while dial and drive disagree.
  • Status. state() reads the status word byte by byte: ST3 (moving, stall) and ST2 (energised, limits), ~90 ms each on a real drive instead of ~250 ms for the whole word, and ST1 only while homing. ST bit 17 (POSMAIN correction) stays set until the next move command, so it is not taken as "moving".
  • Caching. Every query costs 70–90 ms on a real daisy chain, and Bliss reads position and state several times around each move. The controller reuses a stopped axis's position for up to 2 s (POSITION_TTL) and its state for 0.5 s (STATE_TTL), as long as nothing is sent to that drive; any command clears both, and the first read after a move goes to the drive. During a move the position is read again every 0.5 s (MOVING_REFRESH), so umv shows it on the way while short scan steps cost no extra query. A position changed by another program (e.g. spec) is noticed at most 2 s later.
  • Limits. ST bits 13/14 ("limit seen during last move") are reported as LIMNEG/LIMPOS, so a move stopped by a limit raises AxisOnLimitError. hw_limit(±1) and home(±1) take the direction in motor (hardware) sense, as IcePAP does.
  • Encoders. An encoder on a drive's X2 input is a Bliss encoder with an address, read as PA. Axes using it with encoder: $enc and read_position: encoder take their position from it, and Bliss corrects each move's target by the commanded-minus-encoder difference. In that mode Bliss's own discrepancy check compares the encoder with itself, so it never trips. The per-axis max_encoder_error (user units) restores spec's slop: a move is refused when encoder and commanded position differ by more. Lost steps accumulate in that difference until the axis is re-homed or re-zeroed (axis.dial = 0 zeroes encoder and commanded position together). The drive's own position maintenance (POSMAIN) would correct the same error a second time, so start-up aborts if it is armed on an encoder-mode axis.
  • Load-mounted encoders (LOADENC). On a drive with LOADENC on (ST bit 29), positions, velocity and acceleration are in load-encoder counts. The controller then converts velocity and acceleration with the system variable EM (counts per "rev") instead of the motor resolution. Such drives usually run position maintenance (POSMAIN) as well. Use the default read_position: controller and let the drive correct itself. An encoder on the axis still lets Bliss flag an encoder/drive mismatch at the end of a move.
  • Unsupported. SCALE enabled on a drive (start-up aborts), and trajectories.
  • gevent. The controller passes a gevent.lock.RLock to the bus. Bliss patches gevent without threads, so a threading.RLock would let greenlets interleave transactions (verified: timeouts with it, none with the gevent lock).

XRD-3003TT configuration (from spec)

bliss_config/xrd3003tt_vix.yml holds the six ViX axes, translated from the spec config. These were checked on the instrument (2026-10-06, examples/verify_addresses.py):

  • Addresses. Drive address = spec channel + 1. The drive positions matched spec's dial values.
  • Names and units. spec's phi (MOT003) is an x translation in mm and is called x in Bliss. th, tth and chi are in degrees; x, y and z in mm.
  • Signs and limits. x and z use sign: -1, spec's user/dial sign. The limits are spec's dial limits, except x: ±10 mm since 2026-10-09, after a wrong alignment correction drove the stage into the setup.
  • th/tth run LOADENC with EM = 2000 and POSMAIN armed (AR1 DB1). Positions are in encoder counts, 2000 per degree, and the drive corrects itself.
  • Speeds. Velocities and accelerations are spec's slew and ramp, except that x and y accelerate at 4 mm/s² (0.5 s to 2 mm/s; spec: 16 mm/s²).
  • Serial port. For a local device (url: /dev/...) the controller opens the port with pyserial. Through bliss.comm's Serial, the echo of the longer commands such as 1W(CQ,0) lost its first bytes on the real drives, which never happened with pyserial, also inside Bliss. Remote URLs (ser2net, rfc2217, tango) still use bliss.comm.
  • STATUS timing. A real drive sends STATUS over about 3.3 s, with gaps of up to 0.3 s between lines. status_report() waits 1 s for each line.

User offsets are not in the config. After the first start, set each axis to spec's user value (axis.position = ...).

Tests

The tests run against a simulated drive and need no hardware or pyserial:

python -m unittest discover -s tests

tests/bliss_e2e.py runs Bliss axes against the simulator over a pseudo-terminal (tests/pty_sim.py) through a Beacon server. Setup steps are in its docstring; the config is examples/bliss_vix_sim.yml. tests/bliss_e2e_xrd.py runs the instrument config with drives 1/2 set up like the real ones (LOADENC, EM, POSMAIN). tests/bliss_e2e_encoder.py covers Bliss-side encoder correction (tests/encoder_mode_config.yml): reading from the encoder, correcting lost steps, the max_encoder_error check, re-zeroing, homing, and the POSMAIN conflict.

Use on hardware

Since October 2026 the driver runs the XRD-3003TT diffractometer: six ViX500IM drives on one RS232 daisy chain at 9600 baud, two of them with load encoders (LOADENC) and position maintenance (POSMAIN). Moves, status, the daisy-chain echo, LOADENC velocities and the position caching are confirmed there; the timing notes above come from those drives.

Not exercised on hardware yet, and taken from the manual's examples:

  • homing and limit searches, and jogging;
  • the inputs(), LIMITS, HOME and PROFILE0 reply formats;
  • whether EX=2 still sends *E for rejected commands.