Stops a machine and its guests in order — on power loss, a reboot, or anything else that asks it to stop.
Not GA. This is being actively experimented with on one estate. Interfaces and flags will change without ceremony. The reversible half runs on a real node; the irreversible tail — releasing storage mounts, the poweroff itself, and the UPS power-cut backstop — has never been executed outside a rehearsal. Read it, borrow from it, but do not point it at anything you are not prepared to lose.
A UPS gives you minutes, and a stock poweroff spends them badly. A hypervisor
halted without asking yanks its guests rather than stopping them, so nothing
inside ever receives SIGTERM. A Kubernetes node stalls for minutes on CSI mounts
whose backing network is already gone, then gets reset. Both produce the unclean
stop that makes recovery unsafe.
CryoSheep answers exactly one question — how does this machine stop cleanly — and leaves the other two to whoever already owns them:
| question | owner |
|---|---|
| are the mains out? | the UPS, via NUT |
| should this machine stop now? | upsmon, systemd, or an operator |
| how does it stop cleanly? | CryoSheep |
It is invoked, never resident, and strictly local: it never reaches across a host boundary. A sequencer that shuts down its own host cannot finish a loop over others, and a tool that can stop machines it does not live on can stop the wrong one.
Records which workloads held authority while the cluster is still whole. Cordons
the node — never drains it, because in a full shutdown there is nowhere for a
database primary to go except another machine that is also stopping. Releases CSI
mounts before the network disappears, which is what a stock shutdown stalls on.
Stops guests over ACPI (qm shutdown, not qm stop) in reverse Proxmox
startup: order=, honouring each guest's own down= budget. Arms the UPS's own
power-off first, as a backstop for a sequence that cannot finish.
And it undoes all of it if mains return before the point of no return.
curl -fsSL -o /tmp/cryosheep.tar.gz \
https://gitlab.prplanit.com/PrPlanIT/CryoSheep/-/releases/latest-dev/downloads/CryoSheep-latest-dev-linux-amd64.tar.gz
tar xzf /tmp/cryosheep.tar.gz -C /usr/local/bin cryosheep
rm /tmp/cryosheep.tar.gz
cryosheep versionReplace latest-dev with a release tag for a pinned build.
The binary alone does nothing until something invokes it. See deploy/
for the two systemd units and the upsmon wiring.
plan reads the host and prints what would happen. It changes nothing, needs no
configuration, and is safe on a production machine:
cryosheep planIt reports the roles it detected, every guest with its startup order, the ordered sequence, and where the point of no return falls.
To rehearse without acting — including the shutdown-handler path, which is the one that runs most often and that nobody can watch while it happens:
INVOCATION_ID=rehearsal cryosheep sleep --dry-runplan |
show what would happen; changes nothing |
conserve |
shed load and hold, reversibly — upsmon NOTIFYCMD, ONBATT |
cancel |
abandon a sleep and undo it — NOTIFYCMD, ONLINE |
sleep |
the whole sequence — SHUTDOWNCMD, or a unit's ExecStop |
wake |
revive after stasis — on boot |
calibrate |
recommend a deadline from what past runs actually cost |
Three flags, all optional:
--dry-run |
walk and record the decisions without performing them |
--ups-deadline |
when the UPS cuts power regardless — CRYOSHEEP_UPS_DEADLINE |
--kubeconfig |
identity for kubectl — CRYOSHEEP_KUBECONFIG |
Everything else is either a constant or something another system already owns: the
UPS connection is read from /etc/nut/upsmon.conf, the per-guest budget from
Proxmox startup: down=, and why the machine is stopping from the environment of
whatever invoked it. A flag that can contradict the truth is worse than no flag.
Installed as a systemd unit, the teardown runs however the machine is stopped:
systemctl poweroff |
teardown, then systemd halts |
systemctl reboot |
teardown, then systemd reboots — no poweroff |
qm shutdown from the hypervisor |
teardown, then systemd halts |
ansible.builtin.reboot |
teardown, then reboot |
upsmon SHUTDOWNCMD |
full sequence, including poweroff |
systemctl stop cryosheep-stasis |
nothing |
That last row is deliberate. ExecStop fires whenever the unit stops, so stopping
it by hand would otherwise cordon a healthy node and release its mounts. CryoSheep
asks systemd whether a shutdown is actually in progress and declines when it is not.
Four rules, each because the alternative fails badly during a power cut.
The sequence always reaches the end. A step that errors is recorded and the walk continues — a host left running until the battery is flat is worse than any single step failing.
Only a positive reading aborts. Mains observed back before the point of no return abandons the sequence and reverses it. Being unable to read the UPS changes nothing in either direction: blindness must never alter a decision.
Gates stop once committed. They run before every reversible step and before the committing one, then cease. Re-checking after that could only add a way to hang.
It undoes its own actions and nothing else. A noout or a cordon an operator
set by hand is not CryoSheep's to clear — which is also what keeps it out of the
way of a maintenance playbook that cordons first.
Structured lines on stderr. systemd captures them, and every line is forced to disk with an explicit journal sync before the next step begins — journald's own sync interval is five minutes, and a power cut inside that window loses exactly the tail worth having.
There is no second copy and no file of its own. A parallel record with its own rotation is one that nothing ships and nobody reads.
journalctl -t cryosheep -b -1 # the previous boot, on the machine itselfA run that was cut leaves a step.start with no step.end. That absence is the
evidence, and wake reports it on the way back up.
At a terminal the same run reads as prose rather than JSON:
09:24:42 quorum.record dungeon-chest-004
09:24:42 recorded 33 workloads
09:24:42 done 382ms
09:24:42 cordon dungeon-chest-004
09:24:42 skipped 4ms
09:24:42 run complete in 434ms
The UPS deadline should be measured, not chosen. It sits between two failure modes: too short cuts power mid-flush and produces the unclean stop everything else exists to prevent; too long and the battery is flat before it fires.
cryosheep calibrateIt reads past runs back out of the journal, recommends from the worst observed run plus a margin, excludes runs that were cut short, and refuses a recommendation that does not fit the battery. Runtime rather than charge percent, because runtime already folds load in.
systemctl disable --now cryosheep-stasis.service cryosheep-wake.service
rm -f /etc/systemd/system/cryosheep-stasis.service /etc/systemd/system/cryosheep-wake.service
rm -f /usr/local/bin/cryosheep
systemctl daemon-reloadIt keeps no state of its own — the record lives in journald under journald's own
retention. If you wired it into upsmon, remove that too; CryoSheep does not
install it and will not remove it: