function mpc = case9modsolved
%CASE9MODSOLVED
%% MATPOWER Case Format : Version 2
mpc.version = '2';
%%----- Power Flow Data -----%%
%% system MVA base
mpc.baseMVA = 100;
%% bus data
% bus_i type Pd Qd Gs Bs area Vm Va baseKV zone Vmax Vmin
mpc.bus = [
1 3 0 0 0 0 1 1.04 0 345 1 1.1 0.9;
2 2 0 0 0 0 1 1.025 9.27974388 345 1 1.1 0.9;
3 2 0 0 0 0 1 1.025 4.66472921 345 1 1.1 0.9;
4 1 0 0 0 0 1 1.02570288 -2.21668125 345 1 1.1 0.9;
5 1 25 6.25 0 0 1 0.995522393 -3.98984468 345 1 1.1 0.9;
6 1 90 22.5 0 0 1 1.01256119 -3.68813683 345 1 1.1 0.9;
7 1 0 0 0 0 1 1.02563256 3.71905785 345 1 1.1 0.9;
8 1 50 12.5 0 0 1 1.015759 0.726257755 345 1 1.1 0.9;
9 1 0 0 0 0 1 1.03225648 1.96585425 345 1 1.1 0.9;
];
%% generator data
% bus Pg Qg Qmax Qmin Vg mBase status Pmax Pmin Pc1 Pc2 Qc1min Qc1max Qc2min Qc2max ramp_agc ramp_10 ramp_30 ramp_q apf
mpc.gen = [
1 80 27.070218 300 -300 1.04 100 1 250 10 0 0 0 0 0 0 0 0 0 0 0;
2 20 6.61201278 300 -300 1.025 100 1 300 10 0 0 0 0 0 0 0 0 0 0 0;
3 65 -10.8402222 300 -300 1.025 100 1 270 10 0 0 0 0 0 0 0 0 0 0 0;
];
%% branch data
% fbus tbus r x b rateA rateB rateC ratio angle status angmin angmax Pf Qf Pt Qt
mpc.branch = [
1 4 0.0001 0.0576 0.0001 250 250 250 0 0 1 -360 360 71.6786 27.0702 -71.6732 -23.9544;
2 7 0.0001 0.0625 0.0001 250 250 250 0 0 1 -360 360 163.0000 6.6120 -162.9747 9.2090;
3 9 0.0001 0.0586 0.0001 300 300 250 0 0 1 -360 360 85.0000 -10.8402 -84.9930 14.9250;
4 5 0.01 0.085 0.176 250 250 250 0 0 1 -360 360 40.9569 22.9177 -40.6991 -38.7055;
4 6 0.017 0.092 0.158 250 250 250 0 0 1 -360 360 30.7163 1.0367 -30.5497 -16.5463;
5 7 0.032 0.161 0.306 250 250 250 0 0 1 -360 360 -84.3009 -11.2945 86.6004 -8.3940;
6 9 0.039 0.17 0.358 150 150 150 0 0 1 -360 360 -59.4503 -13.4537 60.8039 -18.0722;
7 8 0.0085 0.072 0.149 250 250 250 0 0 1 -360 360 76.3743 -0.8150 -75.8990 -10.6823;
8 9 0.0119 0.1008 0.209 150 150 150 0 0 1 -360 360 -24.1010 -24.3177 24.1892 3.1472;
];
%%----- OPF Data -----%%
%% area data
% area refbus
mpc.areas = [
1 1;
];
%% generator cost data
% 1 startup shutdown n x1 y1 ... xn yn
% 2 startup shutdown n c(n-1) ... c0
mpc.gencost = [
2 1500 0 3 0.11 5 150;
2 2000 0 3 0.085 1.2 600;
2 3000 0 3 0.1225 1 335;
];